Satel INTEGRA Plus Specifications Page 57

  • Download
  • Add to my manuals
  • Print
  • Page
    / 82
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 56
SATEL INTEGRA Plus 55
4.9 Output state indicating
In case of the 24. MONO
SWITCH
, 25. BI
SWITCH
and 64...79
R
EMOTE SWITCH
1...16 type
outputs, the output status can be presented according to the zone status. This is useful, if the
control panel output is to only pass a control pulse to switch the device on/off, and the
information on the current state of the device is supplied to the control panel zone.
You can define how the output status will be presented:
using the keypad, in the service mode, by means of the O
UTS STATE BY
function (O
UTPUT
GROUPS
O
UTS STATE BY
);
using the D
LOAD
X program, in the "Output groups" window, "Output state indicating" tab (to
open the window, press the "Output groups" button in the "Outputs" window).
The output status cannot be presented according to the zone 256 status.
4.10 Logical functions of outputs
It is possible to use any number of outputs as virtual outputs to control the 46. O
UTPUTS
LOGICAL
AND or 47. O
UTPUTS LOGICAL
OR type output.
Example of using output functions 46 and 47
1. Assign functions to the outputs which do not physically exist:
output 63: function 1. B
URGLARY
,
output 64: function 23. A
RM
/D
ISARM BEEP
.
2. Program the output 1, to which the siren is connected, as 47. O
UTPUTS LOGICAL
OR, and
select the outputs 63 and 64 as the controlling ones. The output 1 will be turned on, if the
output 63 or 64 is active.
3. Program the output 62, which does not exist physically, as 26. T
IMER
type. Program the
timer, which is to control the output, as a daily one, turned on at 16.00 and turned off at
8.00.
4. Program the output 2, to which the siren is connected, as 46. O
UTPUTS LOGICAL
AND, and
indicate the outputs 1 and 62 as the controlling outputs. As a result, the output 2 will
signal alarms and confirmation of partition arming/disarming, but only from 16:00 to 8:00.
Beyond these hours, the output will be inactive.
4.11 Output testing
Using the function available in the service mode menu in the keypad (O
UTPUTS
T
EST
),
you can test the outputs. After starting the function, the list of system outputs will be
displayed. Select the output to be tested and press the
or key. The keypad will display
a submenu which enables the output testing. By using the
or key, you can
activate/deactivate the output. You can also deactivate the output by means of the numerical
keys. Press
to quit the submenu and return to the list of system outputs.
The output under test will stop performing its previous function (if it was active, it will
be deactivated).
If there are wireless sirens in the system, starting the function of output testing will
unblock the signaling in them (the signaling is normally blocked for the service mode
duration). It should be remembered that the command to block/unblock the signaling is
sent out during polling. This will cause a delay whose duration depends on the
programmed response period.
When testing the control output for ASP-205 wireless siren, it should be remembered
that the signaling is only triggered during the polling.