SATEL INTEGRA Plus 43
CHIME in module – with this option enabled, zone violation can be signaled in partition
keypads, code locks and readers expanders assigned to the same partition as the zone
(the option C
HIME
must be enabled in the expander).
No alarm sign. in keypad – option for 13.
P
ANIC
-
SILENT
zone type. If it is enabled, alarm from
this zone will not be signaled on keypads. Clearing this alarm by means of keypad will not
be possible.
Outputs signaling the silent panic alarm can be deactivated using the C
LEAR LATCHED
OUTPUTS
user function.
Video on disarmed – if this option is enabled, violating the zone when the partition is
disarmed will activate the 15. V
IDEO ON DISARMED
type output.
Video on armed – if this option is enabled, violating the zone when the partition is armed will
activate the 16. V
IDEO ON ARMED
type output.
Bypass disabled – if this option is enabled, the user cannot bypass the zone.
Bypassed if no exit – if this option is enabled, the zone will be automatically bypassed,
when no partition exit is registered during the partition exit delay countdown. The zone will
also be bypassed when the "full + bypasses" arming mode is on (registering a partition exit
is irrelevant then). The zone will be unbypassed after the partition is disarmed.
Alarm if armed – an option for the zone types 64-79. It is available, if the N
O BYPASS IF
ARMED
option is enabled. When it is enabled, violating an armed zone will cause an alarm
(if the partition exit was registered upon arming).
Alarming – option available for the 91. D
ETECTOR MASK
zone type. If enabled, violation of the
zone will additionally trigger an alarm.
Auto-reset 3 – with this option enabled, the zone can trigger up to 3 alarms. As long as the
alarm is not cleared or the partition is not armed/disarmed, violations of the zone will not
trigger any alarm.
Auto-reset 1 – with this option enabled, the zone can trigger only 1 alarm. As long as the
alarm is not cleared or the partition is not armed/disarmed, violations of the zone will not
trigger any alarm.
Clearing Autoreset – with this option enabled, alarm counters for the zones for which the
A
UTO
-
RESET
3
or A
UTO
-
RESET
1 option is enabled can be automatically reset at midnight
(violations of these zones will be able to trigger alarms again).
Pre-alarm – if this option is enabled, alarms from the zone will be verified.
With verification – an option for the zone types 0-2 and 85-86. If it is enabled, alarms from
the zone will be verified.
Alarm from the zone with enabled P
RE
-
ALARM
or W
ITH VERIFICATION
option will be an
unverified alarm, unless during verification (see description of the A
LARM VERIFICATION
TIME
parameter p. 34) an alarm will be caused by another zone with enabled P
RE
-
ALARM
or W
ITH VERIFICATION
option. In such a case, a verified alarm will be triggered.
Bell delay – an option for the zone types 5 and 6. It changes the way of reaction to a zone
violation when armed. If the option is disabled, the alarm from zone will be delayed by
a programmed time period (A
LARM DELAY
). If the option is enabled, the zone will alarm
immediately (event, reporting and telephone messaging), but the loud signaling will be
delayed by a programmed time period (S
IGNALING DELAY
).
Delay in 2&3 type arming – an option for the 3. I
NTERIOR DELAYED
zone type. If the option is
enabled, the zone will be armed and act as a delayed one upon activation of the type 2
(without interior) and type 3 (without interior and without entry delay) arm mode.
Clear alarm – an option for the zone types 81 and 82. With this option enabled, violation of
the zone will clear alarm in the partition, if it is currently indicated.