36 Programming SATEL
Audible alarm after verification [Bell on 2nd] – if this option is enabled, the alarms from
zones with the P
RE
-
ALARM
or W
ITH VERIFICATION
option enabled will only trigger loud alarm
signaling after verification. The unverified alarms will not trigger loud alarm signaling.
Partition timer
Partitions can be controlled with an additional timer, which can be programmed:
in the keypad, using the function available in the user menu ([code] O
PTIONS
PROGRAMMING
P
ARTITION TIMERS
);
in the DLOADX program connected to the control panel, in the "Structure" window,
"System" tab, after clicking on the partition name and then on the "Partition timer" button.
3.3 Zones
The zone is a separated portion of the protected area which can be supervised by a detector
or detectors. A zone can only be assigned to one partition.
The system supports the following zones:
hardwired – on the control panel electronics board, in keypads and expanders.
The number of available hardwired zones is determined by the control panel during
identification procedure.
wireless – when the ACU-100 or ACU-250 controller is connected. The number of
available wireless zones depends on the number of wireless devices registered in the
system and is determined during the procedure of adding the devices.
virtual – zones which physically do not exist, but have been programmed as F
OLLOW
OUTPUT
or are controlled by means of a keyfob.
3.3.1 Assigning zones to a partition
The zones can be assigned to a partition:
using the keypad, in the service mode, by means of the Z
ONES
function (S
TRUCTURE
S
YSTEM
P
ARTITIONS
S
ETTINGS
[Part. Name] Z
ONES
) – see: S
ELECTION FROM THE
MULTIPLE
-
CHOICE LIST
p. 21;
using the D
LOAD
X program:
1. in the "Structure" window, "System" tab, after clicking on the partition name. Click on
the "Add" button to display the list of zones which can be assigned to the selected
partition. Click on the zone which is to be assigned to the partition.
2. in the "Zones" window, "Zones" tab, "Part." column, enter the number of partition to
which the given zone is to be assigned.
3.3.2 Programming the EOL resistor values
The value of end-of-line resistors is programmable within the range from 500 to 15 k (the
sum of preset values may not exceed 15 k).
The value of EOL resistors for the zones on mainboard can be programmed:
using the keypad, in the service mode, by means of EOL
R1
RESISTOR
, EOL
R2
RESISTOR
and EOL
R3
RESISTOR
functions (S
TRUCTURE
H
ARDWARE
EOL
R1
RESISTOR
/ EOL
R2
RESISTOR
/ EOL
R3
RESISTOR
);
using the D
LOAD
X program, in the "Structure" window, "Hardware" tab, after clicking on the
control panel mainboard.
The value of EOL resistors programmed for the mainboard zones applies also to the
zones in the keypads:
INT-KLCD and INT-KLCDR with electronics version 3.2 and firmware version 2.11
(or later),
Page view 37