12 INTEGRA 128-WRL SATEL
Terminals:
AC - power supply inputs (18 V AC)
COM - common ground
OUT1...OUT2 - programmable high-current outputs (if not used, they should be loaded
with 2.2 kΩ resistors)
+KPD - dedicated power supply output for devices connected to keypad bus
(13.6...13.8 V DC)
DTM - keypad bus data
CKM - keypad bus clock
+EX - dedicated power supply output for devices connected to expander bus
(13.6...13.8 V DC)
DT - expander bus data
CK - expander bus clock
AUX - power supply output (13.6...13.8 V DC)
Z1...Z8 - zones
OUT3...OUT8 - programmable low-current outputs, OC type
3.5 CONNECTING KEYPADS AND OTHER DEVICES TO KEYPAD BUS
Up to 8 different keypads or other devices to be connected to keypad bus can be installed in
the system. They are connected in parallel. The data are addressable and all devices
function independently.
The keypad bus terminals on control panel mainboard have designations COM, +KPD, DTM
and CKM. The +KPD output enables powering of the keypad bus devices (the output has
a polymer fuse).
The distance between the keypad or other device to be connected to keypad bus and the
control panel may be up to 300 m. Table 1 shows the number of wires required for correct
connection of devices to the keypad bus, if using a 0.5 mm
2
cross-section straight-through
cable.
+KPD COM CKM DTM
Distance Number of wires
up to 100 m 1 1 1 1
100-200 m 2 2 1 1
200-300 m 4 4 2 2
Table 1.
Fig. 3. Partial view of keypad board - INT-KLCD-GR/INT-KLCD-BL/INT-KLCDR-GR/